174 ADV200 • Functions description and parameters list
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.5 4508 ExtFlt restart time ms UINT16 1000 120 30000 RW FVS
Setting of the time within which the External Fault alarm must be reset in order to perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.6 4510 ExtFlt holdoff ms UINT16 0 0 10000 RW FVS
Setting of the delay between the signalling of the external fault alarm ExtFlt and enabling of the alarm. If an
alarm condition occurs, the drive will wait for the set time before blocking is enabled. If the alarm is removed
within the set time, the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.7 4516 MotorOT pre activity ENUM Ignore 0 4 ERW FVS
Manages activity from motor overtemperature prealarm.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.8 4518 MotorOT pre thr perc UINT16 60 0 100 ERW FVS
Represents the threshold, in % of the value set in IPA 4532 MotorOT thr, at which the motor overtemperature
prealarm trips.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.9 4520 MotorOT src LINK 16 6000 0 16384 RW FVS
Selection of the origin (source) of the signal to be used for the motor overtemperature alarm MotorOT. The
terminal that can be used for this function can be selected from among those listed in the “L_DIGSEL2” selec-
tion list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.10 4522 MotorOT activity ENUM Warning 0 4 RW FVS
Setting of the behaviour of the drive in case of a motor overtemperature alarm MotorOT. This alarm indicates
that the motor temperature is too high.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.11 4524 MotorOT restart ENUM Disable 0 1 RW FVS
Enabling of automatic restart after the motor overtemperature alarm MotorOT.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.12 4526 TMotorOT restart time ms UINT16 1000 120 30000 RW FVS
Setting of the time within which the Motor Overtemperature alarm must be reset in order to perform automatic
restart.