EasyManuals Logo

gefran ADV200 User Manual

gefran ADV200
308 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #177 background imageLoading...
Page #177 background image
ADV200 • Functions description and parameters list 177
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.25 4560 SpdFbkLoss activity ENUM Disable 0 4 RW FV_
Setting of the behaviour of the drive in case of a speed feedback loss alarm SpdFbkLoss. This alarm indicates
the loss of the encoder feedback signals.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.26 4562 SpdFbkLoss holdoff ms UINT16 200 0 10000 RW FVS
Setting of the delay between the signalling of the speed feedback loss alarm condition SpdFbkLoss and the
enabling of the alarm. If an alarm condition occurs, the drive will wait for the set time before enabling the alarm.
If the alarm is removed within the set time, the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.27 4564 SpdFbkLoss threshold rpm INT16 100 5 CALCI RW FVS
For SE (single ended) encoders and with parameters 2110 or 5110 = (3) Control A-B-SE.
The Speed fbk loss [22] alarm control is enabled when the speed reference is higher than the value set in this
parameter
If using incremental digital encoders in single-ended mode, this parameter sets the limit above which the drive
executes the action set with parameter 4560 SpdFbkLoss activity.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.28 4570 Drive ovld activity ENUM Ignore 0 4 ERW FVS
Setting of the behaviour of the drive in case of a drive overload alarm Drive ovld. This alarm indicates that the
drive overload threshold has been reached.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.29 4572 Motor ovld activity ENUM Warning 0 4 ERW FVS
Setting of the behaviour of the drive in case of a motor overload alarm Motor ovld [14]. This alarm indicates
that the motor overload threshold has been reached.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.30 4574 Bres ovld activity ENUM Disable 0 4 ERW FVS
Setting of the behaviour of the drive in case of a braking resistor overload alarm Bres ovld. This alarm indi-
cates that the braking resistor overload threshold has been reached.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop

Table of Contents