178 ADV200 • Functions description and parameters list
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.31 4582 HTsens restart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the drive heatsink overtemperature alarm HeatsinkS OTUT [10].
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.32 4584 HTsens restart time ms UINT16 20000 120 60000 ERW FVS
Setting of the time within which the HeatsinkS OTUT [10] alarm must be reset in order to perform automatic
restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.33 4600 InAir activity ENUM Stop 0 4 ERW FVS
Setting of the behaviour of the drive in case of an intake air overtemperature alarm Intakeair OT [11].This
alarm indicates that the temperature of the intake cooling air is too high.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.34 4602 InAir restart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the intake air overtemperature alarm Intakeair OT [11].
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.35 4604 InAir restart time ms UINT16 1000 120 30000 ERW FVS
Setting of the time within which the Intakeair OT [11] alarm must be reset in order to perform automatic re-
start.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.36 4606 InAir holdoff ms UINT16 10000 1000 30000 ERW FVS
Setting of the delay between the signalling of the intake air overtemperature alarm Intakeair OT [11] and ena-
bling of the alarm. If an alarm condition occurs, the drive will wait for the set time before enabling the alarm. If
the alarm is removed within the set time, the drive will not indicate any alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.37 4610 Desat restart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the desaturation alarm Desat. This alarm indicates a short circuit between
the motor phases or on the power bridge.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.38 4612 Desat restart time ms UINT16 2000 1000 10000 ERW FVS
Setting of the time within which the Desaturation alarm must be reset in order to perform automatic restart.
(Time with alarm signal active + 1000 msec).

Table of Contents

Other manuals for gefran ADV200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran ADV200 and is the answer not in the manual?

gefran ADV200 Specifications

General IconGeneral
Brandgefran
ModelADV200
CategoryInverter
LanguageEnglish

Related product manuals