180 ADV200 • Functions description and parameters list
The output signal UV Wng & Restart goes at high level when an alarm is generated UV Wng & Restart warn-
ing and it returns at low level when the alarm disappear, as indicated above.
Note! If the automatic restart function is required, the start and Enable signals must be active.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.45 4650 UVRep attempts UINT16 5 0 1000 ERW FVS
Setting of the maximum number of attempts at automatic restart after the Undervoltage [2] alarm before a
Mult Undervoltage [6] alarm is generated. If this parameter is set to 1000 an innite number of attempts are
available.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.46 4652 UVRep delay s UINT16 240 0 300 ERW FVS
Setting of the time within which, if no automatic restarts are executed after the Undervoltage [2] alarm, the at-
tempts counter is reset. In this way the number of attempts set in UVRep attempt are still available.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.47 4660 PhLoss activity ENUM Disable 0 4 ERW FVS
Setting of the behaviour of the drive in case of a no phase alarm. This alarm indicates the absence of a drive
power supply phase.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.48 4662 PhLoss restart ENUM Disable 0 1 ERW FVS
Enabling of automatic restart after the no phase alarm.
0 Disable
1 Enable
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.49 4664 PhLoss restart time ms UINT16 1000 120 10000 ERW FVS
Setting of the time within which the Phase loss alarm must be reset in order to perform automatic restart.
(Time with alarm signal active + 100 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.50 4670 Optionbus activity ENUM Disable 0 4 ERW FVS
Setting of the behaviour of the drive in case of an Opt Bus Fault alarm.
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.51 4672 Optbus fault en src LINK 16 6002 0 16384 ERW FVS
Selection of the origin (source) of the signal to be used as “Opt bus fault” [17] alarm. The terminal that can be
used for this function can be selected from among those listed in the “L_DIGSEL1” selection list.
The default is PAR 6002 One. If it is selected the PAR 1030 Local / remote mon, it can inhibit the alarm only
when you switch from “Remote” to “Local”.

Table of Contents

Other manuals for gefran ADV200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran ADV200 and is the answer not in the manual?

gefran ADV200 Specifications

General IconGeneral
Brandgefran
ModelADV200
CategoryInverter
LanguageEnglish

Related product manuals