ADV200 • Functions description and parameters list 181
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.52 4680 Ground Fault thr perc FLOAT 10.0 0 150.0 ERWS FVS
Setting of the threshold for the ground short circuit alarm Ground Fault.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.53 4684 Brake fault activity ENUM Disable 0 4 ERW FVS
This parameter can be used to congure the behaviour of the drive in the event of a mechanical brake fault.
The following activities are programmable:
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.54 4690 ExtIO activity ENUM Disable 0 4 ERW FVS
This parameter is used to congure the behaviour of the drive if the “Ext I/O fault” [27] alarm occurs when the
EXP-FL-XCAN-ADV card is installed.
See Chapter C - “Ext I/O fault” [27] alarm.
When the alarm is activated due to a communication error, the last value that was received is maintained.
The following activities are programmable:
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
You can check whether a card that supports XCAN External IO functions is installed from the DRIVE INFO
menu for parameters 530, 532, 534 SlotX card type:
Value Description Expansion
832 IO FastLink EXP-FL-XCAN-ADV XCAN External IO supported
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.55 4940 FL fault activity ENUM Disable 0 4 ERW FVS
This parameter is used to congure the behaviour of the drive when the “FastLink fault” [28] alarm occurs.
If the EXP-FL-XCAN-ADV card is installed in the drive, all the FastLink communication fault signals are ena-
bled and managed via generation of a “FastLink fault” [28] alarm, with different subcodes to indicate the cause
of the error.
See Chapter C - “FastLink Fault” [28] alarm.
The following activities are programmable:
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.56 4654 Mot PhLoss activity ENUM Ignore 0 4 ERW FV_
The “Motor phase loss” alarm signals the loss of a motor phase. This parameter manages the alarm activity.
0 Ignore
1 Warning
2 Disable

Table of Contents

Other manuals for gefran ADV200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran ADV200 and is the answer not in the manual?

gefran ADV200 Specifications

General IconGeneral
Brandgefran
ModelADV200
CategoryInverter
LanguageEnglish

Related product manuals