278 ADV200 • Parameters List
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.10 4522 MotorOT activity ENUM Warning 0 4 RW FVS
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
24.11 4524 MotorOT restart ENUM Disable 0 1 RW FVS
0 Disable
1 Enable
24.12 4526 MotorOT restart time ms UINT16 1000 120 30000 RW FVS
24.13 4528 MotorOT holdoff ms UINT16 1000 0 30000 RW FVS
24.14 4530 MotorOT probe ENUM SRC 0 13 ERW FVS
0 SRC
1 Sens An1X
2 Sens An2X
3 KTY84 AnX
4 PTC AnX
5 KTY84 An1
6 KTY84 An2
7 PTC An1
8 PTC An2
9 Klixon AnX
10 KTY84 An1X
11 KTY84 An2X
12 PTC An1X
13 PTC An2X
24.15 4514 MotorOT KTY84 unit ENUM ohm 0 1 ERW FVS
0 ohm
1 °C
24.16 4532 MotorOT thr cnt UINT16 0 0 32767 ERW FVS
24.17 4536 MotorOT mon cnt INT16 16/32 0 0 32767 ER FVS
24.18 4540 Overspeed threshold rpm INT32 CALCI 0 CALCI RW FVS
24.19 4542 Overspeed activity ENUM Disable 0 4 RW FVS
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
24.20 4544 Overspeed holdoff ms UINT16 0 0 5000 RW FVS
24.21 4550 SpdRefLoss threshold rpm INT16 100 0 CALCI RW FVS
24.22 4552 SpdRefLoss activity ENUM Ignore 0 4 RW FVS
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
24.23 4554 SpdRefLoss holdoff ms UINT16 1000 0 10000 RW FVS
24.24 4558 SpdRefLoss minThr en BIT 0 0 1 ERW FVS
24.25 4560 SpdFbkLoss activity ENUM Disable 0 4 RW FV_
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
24.26 4562 SpdFbkLoss holdoff ms UINT16 200 0 10000 RW FV_

Table of Contents

Other manuals for gefran ADV200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran ADV200 and is the answer not in the manual?

gefran ADV200 Specifications

General IconGeneral
Brandgefran
ModelADV200
CategoryInverter
LanguageEnglish

Related product manuals