ADV200 • Parameters List 279
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.27 4564 SpdFbkLoss threshold rpm INT16 100 5 CALCI RW FV_
24.28 4570 Drive ovld activity ENUM Ignore 0 4 ERW FVS
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
24.29 4572 Motor ovld activity ENUM Warning 0 4 ERW FVS
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
24.30 4574 Bres ovld activity ENUM Disable 0 4 ERW FVS
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
24.31 4582 HTsens restart ENUM Disable 0 1 ERW FVS
0 Disable
1 Enable
24.32 4584 HTsens restart time ms UINT16 20000 120 60000 ERW FVS
24.33 4600 InAir activity ENUM Stop 0 4 ERW FVS
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
24.34 4602 InAir restart ENUM Disable 0 1 ERW FVS
0 Disable
1 Enable
24.35 4604 InAir restart time ms UINT16 1000 120 30000 ERW FVS
24.36 4606 InAir holdoff ms UINT16 10000 1000 30000 ERW FVS
24.37 4610 Desat restart ENUM Disable 0 1 ERW FVS
0 Disable
1 Enable
24.38 4612 Desat restart time ms UINT16 2000 1000 10000 ERW FVS
24.39 4620 IOverC restart ENUM Disable 0 1 ERW FVS
0 Disable
1 Enable
24.40 4622 IOverC restart time ms UINT16 2000 1000 10000 ERW FVS
24.41 4630 OverV restart ENUM Disable 0 1 ERW FVS
0 Disable
1 Enable
24.42 4632 OverV restart time ms UINT16 2000 1000 10000 ERW FVS
24.43 4640 UnderV restart ENUM Enable 0 1 ERW FVS
0 Disable
1 Enable
24.44 4642 UnderV restart time ms UINT16 1000 120 10000 ERW FVS
24.45 4650 UVRep attempts UINT16 5 0 1000 ERW FVS
24.46 4652 UVRep delay s UINT16 240 0 300 ERW FVS
24.47 4660 PhLoss activity ENUM Disable 0 4 ERW FVS
0 Ignore