82 ADV200 • Functions description and parameters list
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.21 2064 Measured FlxX Wb FLOAT CALCF 0.0 0.0 ERWS FVS
Measured ux saturation value.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.22 2066 Measured P1 FLOAT 0.05 0.0 1.0 ERWS FVS
Measured value of the rst parameter to dene the motor magnetization curve.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.23 2068 Measured P2 FLOAT 9.0 3.0 18.0 ERWS FVS
Measured value of the second parameter to dene the motor magnetization curve.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.24 2070 Measured P3 FLOAT 0.87 0.0 1.0 ERWS FVS
Measured value of the third parameter to dene the motor magnetization curve.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.25 2072 Measured Rr ohm FLOAT CALCF 0.0005 200.0 ERWS FVS
Measured rotor resistance value.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.26 2078 Take tune parameters BIT 0 0 1 ERWZ FVS
Saves the motor data calculated by the self-tuning procedure in the drive.
Note ! Data are not saved permanently. Use the “Save Parameters” command in the DRIVE CONFIG menu to save in the permanent
memory.