www.gemu-group.com22 / 71GEMÜ 1435 ePos
11 Assembly
ð The cable must be held firmly on all sides.
9. Connect the pneumatic supply to the positioner and con-
nect to the quarter turn actuator 3.
11.4 Checking the mechanical mounting
1. Connect the product to the power and air supply (see elec-
trical connection and pneumatic connection).
2. The following message is displayed:
3. By pressing the and keys, the mounted actuator
can be moved to the OPEN and CLOSED position.
4. Important: The displayed valve position must be between
2% and 98%. If the display leaves this area, check the
mechanical mounting again and, if necessary, readjust the
orientation of the rotary travel sensor. In the case of linear
travel sensors, check the mounting parts used for compat-
ibility.
NOTICE
Note for the rotary travel sensor
The slotted holes should be positioned in the centre on
the screws. If the travel range is incorrect (determined by
checking the attachment), loosen the two screws slightly
and twist the travel sensor. Set the travel up correctly and
tighten the screws again.