www.gemu-group.com 33 / 71 GEMÜ 1435 ePos
16.2 Parameter table
Display Function Value range Unit Default setting
1:SETPOINT Type of set value 0..10 V
0..20 mA
4..20 mA
V
mA
mA
4..20 mA
2:INIT ALL Starting automatic initialization NO INIT
Init OK
- NO INIT
3:DEFAULT STATE Return to default setting NO DEFAULT
DEFAULT
- DEFAULT
11:X-DIRECTION Direction of X display and actual
value output
RISE
FALL
RISE
12:ALARM FUNCT Defines the function of the alarm
outputs (ALARM1 and ALARM 2)
OFF
min/max
min/min
max/max
OFF
13:LEVEL ALARM1 Switch point of alarm 1 0.0...100.0 10.0
14:LEVEL ALARM2 Switch point of alarm 2 0.0...100.0 90.0
15:ERROR FUNCTN Defines the function of the error
message output (ERROR)
ERROR
ERROR+ INACTIVE
RANGE
ERROR+RANGE
ERR+RANGE+INAC
ERROR+RANGE
16:ERROR TIME Valve travel time monitoring
(Error message output)
auto
0...100
s auto
17:ERROR LEVEL Maximum system deviation
(Error message output)
auto
0.0...100.0
% auto
18:RANGE FUNCTN Range monitoring of set value in-
put
< 4 mA
> 20 mA
< 4 mA or > 20 mA
mA < 4 mA or > 20 mA
21:MIN POSITION Limits the CLOSED position of the
valve min. position
0.0...100 % 0.0
22:MAX POSITION Limits the OPEN position of the
valve max. position
0.0...100 % 100.0
23:CLOSETIGHT Defines the function of the close
tight function
no
min
max
min & max
no
24:SETP DIRECTN
1)
Direction of set value NORMAL
INVERSE
NORMAL
25:SETP RAMP Ramp function - set value auto
0...400
s 0
26:SPLIT START Split range (set value range) start 0.0 ... 90 % 0.0
27:SPLIT END Split range (set value range) end 10 ... 100 % 100
28:SETP FUNCTN Defines the function of the control
characteristic
Linear
1:25
1:50
free
Linear
16 System mode CLASSIC