www.gemu-group.com54 / 71GEMÜ 1435 ePos
17 System mode ADVANCED
17.2.4.3 Changing the default setting for 2 SetBasics
Display Function Default setting
SetPoint Type of set value signal 4–20 mA
D.Refresh Time for display refresh 0.5 s
System mode Type of operator interface Classic
DLight Setting the display lighting OnKey
DLightTime Time for switching off display
lighting during adjustment [On-
Key]
5 min
HelpLanguage Text language D
HelpText Display the help text ON
17.2.5 Menu 3 SetFunction
Level Alarm2 90.0 %
0.0...100.0 %
Level Alarm1 10.0 %
0.0...100.0 %
PosCtrl
SetFunction
3
Position Output
Return
Return
Return
Prop Gain 1.0
0.1...100.0
CpyParaSet OFF
P1<=W
P1=>P2
P1<=P2
P1=>P3
P1<=P3
P1=>P4
P1<=P4
Deriv Time 0.1 s
0.01...1 s
Dead Band Auto
0.0...10.0 %
Min Pos 0.0 %
0.0...100.0 %
Max Pos 100.0 %
0.0...100.0 %
Close Tight no
no
min
max
min & max
Alarm Fn OFF
OFF
min/max
min/min
max/max
Error Level... Auto
0.0...100.0 %
Error Time Auto
0.0...100.0 s
Error Functn Error
Error+Inactive
Range
Error+Range
Err+Range+Inac
Range Functn <4mA or >20mA
< 4mA
> 20mA
<4mA or > 20mA
Alarm Output
Return
Error Output
Out max 100.0 %
0.0...100.0 %
Out min 0.0 %
0.0...100.0 %
Analog Out 0-10V
0-20mA *
4-20mA *
Return
17.2.5.1 Parameter table for 3 SetFunction
NOTICE
▶ Certain Active Levels are required (see “Activating or deactivating user access“, page47) in order to read and edit the para-
meters.
Display Function Value range Default setting Active level
Read Edit
PosCtrl Submenu for setting
positioner paramet-
ers (see “PosCtrl“,
page55)
DeadBand Permissible system
deviation
0.0...10%
auto
1.0%,
K-no. 2442: 2.0%
K-no. 2443: 5.0%
0 2
AlarmOutput Submenu for setting
the alarm outputs
(see “AlarmOutput“,
page56)