www.gemu-group.com 41 / 71 GEMÜ 1435 ePos
17.2.2 Parameter overview
Menu levels Submenu Display Function Value range Default setting
Mode Select operating mode AUTO AUTO
MAN
OFF
1 Service I/O status Submenu for displaying inputs and outputs
min-Pot-max Displays travel sensor
position in percent
I w / U w Value of set value signal
in mA / V
W Pos X Comparison of set value
and valve position
Pot Abs Travel sensor position
Valve Displays the current posi-
tion of the internal pilot
valves
Pos Ctrl Out Deviation between set
value and actual value
(positioner)
Relais K1:K2:Err Displays the current posi-
tion of the internal out-
puts
Login Submenu for setting access authorisations
Code Password entry 0 ... 10000 0
Logout Block access OK
New Code: 1 Release the lowest prior-
ity
0 ... 10000 0
New Code: 2 Release the medium pri-
ority
0 ... 10000 0
New Code: 3 Release the top priority 0 ... 10000 0
Diagnosis Submenu for displaying diagnostic messages
Error List Displays error messages
hrs Displays operating hours
Warnings Display warnings during
operation
ON / OFF ON
Errors Display errors during op-
eration
ON / OFF ON
Clear Error List Delete error list OK
1435 specific Submenu for displaying the tool identification
Release Shows the current soft-
ware release
S/N Displays current serial
number
TAG1 11-digit ID number can
be set
TAG2 11-digit ID number can
be set
2 SetBasics
Setpoint Type of set value signal 4–20 mA / 0–20
mA / 0–10 V
4–20 mA
Default Reset to default settings Yes / No Yes
17 System mode ADVANCED