17.2.6 Menu 4 SetCalibration
W 0% 2.0 %
0.0...100.0 %
SetCalibration
4
Return
X-DIR: RISE
RISE...FALL
SetpDir: NORMAL
NORMAL
INVERS
W 10% 3.0 %
0.0...100.0 %
W 40% 9.6 %
0.0...100.0 %
W 90% 67.7 %.
0.0...100.0 %
W 20% 4.4 %
0.0...100.0 %
W 70% 30.9 %...
0.0...100.0 %
W 50% 14.1 %
0.0...100.0 %
W 100% 100.0 % ...
0.0...100.0 %
W 30% 6.5 %
0.0...100.0 %
W 80% 45.7 %...
0.0...100.0 %
W 60% 20.9 %...
0.0...100.0 %
Setp Fn: linear
linear
1:25
1:50
free
Setp Ramp: 0s
0...400 s
Split Start: 0.0 %
0.0...100 %
Split End: 100.0 %
0.0...100 %
Return
Setp Fn
17.2.6.1 Parameter table for 4 SetCalibration
NOTICE
▶ Certain Active Levels are required (see “Activating or deactivating user access“, page47) in order to read and edit the para-
meters.
Display Function Value range Default setting Active level
Read Edit
X-DIR Direction of X display
and actual value out-
put
RISE
FALL
RISE 0 3
Setp Dir
1)
Direction of set value NORMAL
INVERSE
NORMAL 0 3
Setp Ramp Ramp function - set
value
AUTO
0...400 s
0 s 0 3
Split Start Split range (set value
range) start
0.0...90% 0.0% 0 3
Setp Fn Defines the function
of the control charac-
teristic
Linear / free /
1:25 / 1:50
Linear 0 3
Setp Functn Submenu for setting
the set value calibra-
tion points (only pos-
sible with Setp Fn:
free) (see “Setp
Functn“, page61)
1) Parameter value is automatically calculated and set by the positioner during initialisation. A manual change may have to be repeated after
each initialisation process
17.2.6.1.1 Setp Functn
NOTICE
▶ Certain Active Levels are required (see “Activating or deactivating user access“, page47) in order to read and edit the para-
meters.
Submenu for setting the set value calibration points (only possible with Setp Fn: free)
Display Value range Default setting Active level
Read Edit
W 0% 0...100% 2.0% 0 3
W 10% 0...100% 3.0% 0 3
W 20% 0...100% 4.4% 0 3
W 30% 0...100% 6.5% 0 3
17 System mode ADVANCED