www.gemu-group.com 49 / 71 GEMÜ 1435 ePos
Clear Error List:
Press the key here to delete the error list for the positioner.
17.2.3.2.4 Displaying the serial number and software version, entering the TAG number
I / O Status
1.1
Service
1
SetFunction
3
SetCalibration
4
Communication
5
SetBasics
2
SETUP
Login
1.2
Diagnosis
1.3
Gemü Specific
1.4
V:X.X.X.X:
Displays the current software release
S/N:
Displays the positioner serial number
TAG1:
An 11-digit TAG number can be entered for identification of the positioner.
TAG2:
An 11-digit TAG number can be entered for identification of the positioner.
17.2.4 Menu 2 SetBasics
Init All
Return
Init All
Auto . Man ESC
Setpoint: 4-20 mA
0-20 mA
4-20 mA
0-10 V
Default: Default
Default
No Default
CalPointQty 9
1...19
D. Refresh 0.5 s
0.1...1.0 s
DLightTime 5min
1...60min
SetBasics
2
Helptext. ON
ON...OFF
HelpLanguage D
D
GB
Systemmode
CLASSIC
ADVANCED
DLight On Key
On Key
On
17.2.4.1 Parameter table for 2 SetBasics
NOTICE
Certain Active Levels are required (see “Activating or deactivating user access“, page47) in order to read and edit the para-
meters.
Display Function Value range Default setting Active level
Read Edit
Setpoint Type of set value sig-
nal
4–20 mA
0–20 mA
0–10 V
4–20 mA 0 3
Default Reset to default set-
tings
Yes / No Yes 3 3
17 System mode ADVANCED