www.gemu-group.com50 / 71GEMÜ 1435 ePos
17 System mode ADVANCED
Display Function Value range Default setting Active level
Read Edit
Init All Submenu for carrying
out the initialization
(see “Init All“,
page50)
CalPointQty Quantity of calibration
points when initializ-
ing
1...19 2 3 3
D.Refresh Time for display re-
fresh
0.1...1.0 s 0.5 s 0 1
System mode Type of operator inter-
face
CLASSIC / AD-
VANCED
CLASSIC 0 3
DLight Setting the display
lighting
OnKey / On OnKey 0 2
DLightTime Time for switching off
display lighting during
adjustment [OnKey]
1...60 min 5 min 0 2
HelpLanguage Text language D / GB D 0 1
HelpText Display the help text ON/OFF ON 0 1
17.2.4.1.1 Init All
NOTICE
▶ Certain Active Levels are required (see “Activating or deactivating user access“, page47) in order to read and edit the para-
meters.
Submenu for carrying out the initialization
Display Function Value range Default setting Active level
Read Edit
goClose Scanning the closed
position
3 3
GoOpen Scanning the open
position
3 3
AdjTime Scanning the travel
times
3 3
findCoefficent Optimization of con-
trol characteristics
3 3
InitPilot Setting the minimum
travel times for in-
ternal pilot valves
3 3
17.2.4.2 Explanation of parameters for 2 SetBasics
17.2.4.2.1 Definition of set value input
Set Point
Range of analogue set value input (Voltage: 0-10 V or power: 0/4-20 mA).
17.2.4.2.2 Reset
NOTICE
Setting to default
▶ After setting to Default, the product must be reinitialized. All actuation parameters established so far are deleted. . The
parameters D.Refresh and the New Code 1-3 are not taken into account.