www.gemu-group.com 65 / 71 GEMÜ 1435 ePos
17.2.6.3 Changing the default setting for 4 SetCalibration
Display Function Default setting
X-Direction Direction of X display and ac-
tual value output
RISE
Setp Direction Direction of set value NORMAL
Setp Ramp Ramp function - set value 0 s
Split Start Split range (set value range)
start
0.0%
Split End Split range (set value range)
end
100%
Setp Function Defines the function of the
control characteristic
Linear
W 0% 2.0
W 10% 3.0
W 20% 4.4
W 30% 6.5
W 40% 9.6
W 50% 14.1
W 60% 20.9
W 70% 30.9
W 80% 45.7
W 90% 67.6
W 100% 100
17.2.7 Menu 5 Communication
The Communication menu has no function.
Communication
5
Return
Fieldbus SETP.ANALOG
SETP.ANALOG
SETP.BUS
17 System mode ADVANCED