www.gemu-group.com 35 / 71 GEMÜ 1435 ePos
16.3 Explanation of parameters
1: Set Point
Range of analogue set value input (Voltage: 0-10 V or power:
0/4-20 mA).
2: Init All
Initialization
Press and press and hold the key (> 3 sec) to start the
automatic initialization. The progress of the initialization is
shown with RUN 1 to RUN 5 in the display.
During the initialization process, the positioner optimizes its
control parameters for controlling the valve concerned.
NOTICE
This process must be carried out in order to be able to se-
lect automatic or manual operation and should be re-
peated after every change to the mechanical end posi-
tions (e.g. seal replacement on the valve/operator re-
placement).
3: Default State
Default setting
Return to default setting and reset initialization. Press
and press and hold the key (> 3 sec) to set the controller
to Default.
NOTICE
Setting to default
After setting to Default, the product must be reinitialized.
All actuation parameters established so far are deleted.
The parameters D.Refresh and the New Code 1-3 are not
taken into account.
11: X-Direction
Correcting variable direction
Here the display direction (rising or falling) and the position
feedback can be adjusted.
X-DIRECTION Valve position Displayed
value
Allocated ac-
tual position x
CLOSED RISE 0% 0%
OPEN 100% 100%
CLOSED FALL 100% 100%
OPEN 0% 0%
12: Alarm Functn
Activates or deactivates the alarm function
The reaction of the alarms (limiting contacts) relates to the
position measurement (mechanical distance).
x = current actual value
Min/Max:
Item State output
A1
State output
A2
x < Level Alarm1 < Level
Alarm2
24 V 0 V
Item State output
A1
State output
A2
Level Alarm1 < x < Level
Alarm2
0 V 0 V
Level Alarm1 < Level Alarm2 <
x
0 V 24 V
Min/Min:
Item State output
A1
State output
A2
x < Level Alarm1 < Level
Alarm2
24 V 24 V
Level Alarm1 < x < Level
Alarm2
0 V 24 V
Level Alarm1 < Level Alarm2 <
x
0 V 0 V
Max/Max:
Item State output
A1
State output
A2
x < Level Alarm1 < Level
Alarm2
0 V 0 V
Level Alarm1 < x < Level
Alarm2
24 V 0 V
Level Alarm1 < Level Alarm2 <
x
24 V 24 V
13: Level Alarm 1
Switch point for Alarm 1. When the switch point has been
reached, digital output A1 (24 V DC output) is switched.
14: Level Alarm 2
Switch point for Alarm 2. When the switch point has been
reached, digital output A2 (24 V DC output) is switched.
15: Error Functn
Function of the error message output (24 V DC output)
The table shows which functions are relevant to the setting of
the output at which setting value.
Setting Error
Time
Error
Level
Range
Functn
C: Config
Error X X
Error+
Inactive
X X X
Range X
Error+
Range
X X X
Error+
Range+
Inactive
X X X X
16 System mode CLASSIC