www.gemu-group.com48 / 71GEMÜ 1435 ePos
17 System mode ADVANCED
The codes can be changed or activated in the following menu:
I / O Status
1.1
Service
1
Login
1.2
Return
Code: 0
Active Level: 3
(0...10000)
Logout?
OK
NewCode:1 0
0...10000
NewCode:2 0
0...10000
NewCode:3 0
0...10000
Code:
Enter code for user access. The currently released user level is displayed at Active Level.
Example: In Active Level 0, the positioner is disabled in all three user levels.Only the parameters marked by the symbol r0w0
can be read and changed.
Logout:
Used for logging out of write-protected and read-protected areas in the menu. This function disables various menus depending
on the user level activated. User level 0 is displayed in parameter Active Level.
New Code 1:
Enter the new code for the lowest user level (user level 1) (default setting 0).
New Code 2:
Enter the new code for the medium user level (user level 2) (default setting 0).
New Code 3:
Enter the new code for the highest user level (user level 3) (default setting 0).
NOTICE
▶ Default setting 0 means that all three codes are assigned 0. This means that all parameter menus are released.
Example: If user level 2 is to be disabled, user level 2 and also user level 3 must be assigned a code.
17.2.3.2.3 Reading out, deleting and deactivating error messages
I / O Status
1.1
Service
1
SetFunction
3
SetCalibration
4
Communication
5
SetBasics
2
SETUP
Login
1.2
Diagnosis
1.3
Error List:
The positioner stores the last 100 error messages in this menu. The errors are also stored in the error memory in the operator
interface during operation.
hrs:
The operating hours of the positioner are counted here.
Warnings:
The warning messages can be masked or displayed here.The positioner continues normal operation when a warning is given.
Messages are stored in ErrorList.
Errors: