www.gemu-group.com 55 / 71 GEMÜ 1435 ePos
Display Function Value range Default setting Active level
Read Edit
ErrorOutput Submenu for setting
the error output (see
“ErrorOutput“,
page56)
PositionOutput Submenu for setting
the actual value out-
put (see “Position-
Output“, page56)
CpyParaSet Copies parameters to
the working memor-
ies (P1/P2/P3/P4)
3 3
17.2.5.1.1 PosCtrl
NOTICE
Certain Active Levels are required (see “Activating or deactivating user access“, page47) in order to read and edit the para-
meters.
Submenu for setting positioner parameters
Display Function Value range Default setting Active level
Read Edit
Prop Gain
1)
P amplification of the
positioner
0.1...100.0 X.X 0 3
DerivTime Decay time of the D
component of the po-
sitioner
0.00...10.00 s 0.1 s 0 3
MinPos Seal adjuster = lower
pos. control ranges
0...100% 0.0% 0 3
MaxPos Stroke limiter = upper
pos. control ranges
0...100% 100% 0 3
CloseTight Close tight function no
Min / Max
Max.
Min.
no 0 3
1) Parameter value is automatically calculated and set by the positioner during initialisation. A manual change may have to be repeated after
each initialisation process
17 System mode ADVANCED