www.gemu-group.com 53 / 71 GEMÜ 1435 ePos
- In order to prevent incorrect operation, the parameters from manual initialization are only accepted when they comply with the
requirements for correct function.
Go Close:
The closed valve position is scanned during initialization.
In the case of manual initialization, this must be confirmed with the key .
Go Open:
The open valve position is scanned during initialization.
In the case of manual initialization, this must be confirmed with the key .
AdjTime:
Wird nur angezeigt, wenn goOpen und goClose durchgeführt wurden.
Die minimalen Stellzeiten des Ventils werden während der Initialisierung abgefragt.
Bei der manuellen Initialisierung muss diese mit der Taste bestätigt werden.
Find Coefficient:
Only displayed if adjTime was carried out.
The valve is checked for control features at various positions between the end positions.
Init Pilot:
The minimum travel times for the internal pilot valves are adjusted to the process valve.
In the case of manual initialization, this function must be started by pressing the key .
Call Point Qty:
The quantity of calibration points when initializing can be changed.
Example: QtyCalPoint=9 means: The valve will be examined for control features between the end position stops in 9 positions
(10% steps here).
17.2.4.2.4 Making the display settings
D.Refresh:
The time for display refresh can be changed.
System mode:
Selection of operator interface:
- CLASSIC:
Menu configuration as described in chapter CLASSIC system mode (see “System mode CLASSIC“, page31).
- ADVANCED:
Menu configuration as described in chapter ADVANCED system mode (see “System mode ADVANCED“, page38).
DLight:
The features of the display lighting can be switched between the following settings:
- OnKey – Display lighting is activated by pressing a key. The display lighting remains activated after the last key is pressed for
the period set using DLightTime.
- On – The display lighting is permanently activated.
DLightTime:
Time for automatically shutting off the display lighting when the parameter DLight is set to OnKey
HelpLanguage:
The help text language can be selected between D-German and GB-English.
HelpText:
The help texts that appear as a default in the second line of the display can be masked.
If the help texts are masked, the key assignment is displayed.