www.gemu-group.com 63 / 71 GEMÜ 1435 ePos
SetP Ramp
Set value ramp
The set value ramp is effective during automatic operation and limits the speed of change of the effective set value. When
switching over from manual to automatic operation, the effective set value is matched to the set value on the device via the set
value ramp.
In the position SetP Ramp = AUTO, the slower of the two travel times which have been established during initialization is used
for the set value ramp.
Split Start
Set value split range start
Split End
Set value range
controller 1
Set value range
controller 2
Set value
Stroke
Set value split range end
Parameters 26 and 27 in conjunction with parameter 24 serve to limit the effective set value range. In this way split range tasks
with the curves
- rising / falling
- falling / rising
- falling / falling
- rising / rising
are resolved.
NOTICE
Difference between Split Start/End
▶ The difference between the Split Start and Split End values must be > 10%.
17 System mode ADVANCED