EasyManua.ls Logo

GEM 651 - Optical Indication

GEM 651
68 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58 / 68
651
15.3 Optical indication
1
2
3
4
LED Designation Colour
1 OPEN yellow
2 ERROR red
3 CLOSED orange
4 POWER yellow
Meaning Error number
LED 1
OPEN
LED 2
ERROR
LED 3
CLOSED
LED 4
POWER
Position reached -
HHHG
Valve in OPEN end position -
GHHG
Valve in CLOSED end position -
HHGG
Valve moves in OPEN direction -
$HHG
Valve moves in CLOSED direction -
HH$G
Positioner in initialisation phase -
$H$G
Set value > 20.5 mA / 10.25 V Error no. 1
$=HG
Set value < 3.5 mA Error no. 2
H=$G
Positioner not initialised Error no. 3
$=$G
Positioner not calibrated Error no. 4
GGG$
Device error Error no. 5
H=HG
Positioner works with lower quality Warning no. 1
5G
Key LED conditions Flashing frequency
H
LED off
G
LED on
5
LED flashes
briefly f = 1.66 Hz; 0.15 s on / 0.45 s off
=
LED flashes fast f = 3.33 Hz; 0.15 s on / 0.15 s off
$
LED flashes slowly f = 1.66 Hz; 0.30 s on / 0.30 s off