46 Owner’s Manual for Power Zone Pro Sync
Troubleshooting
CAN BATx
MODULE ERROR
The Power Zone Battery Charger
#x is reporting an error over CAN
bus to the Main Controller. The
error message will present an
error number which corresponds
to the error the module is
reporting. See the Battery
Charger manual for each error
message and description.
The Power Zone Battery
Charger detected an error
in its operation and
communicated the alarm
code to the Main Controller
over CAN bus.
Turn the Keyswitch to
OFF. Verify the Power
Zone Battery Charger
error is resolved. Clear
the shutdown alarm
using the Display.
CAN UNKNOWN
MODULE ERROR
A module with an unknown
address reported an error over
CAN bus with the Main Controller.
There may not be a way to tell
which alarm has been triggered
without knowing what module it
came from.
There is a module
communicating over CAN
bus with the Main
Controller that has reported
an error, but the address of
the module is unknown,
corrupted, or invalid.
Turn the Keyswitch to
OFF. Verify the Unknown
module error is resolved.
Clear the shutdown
alarm using the Display.
CAN GOVx
MODULE
WARNING
The Power Zone Governor
module #x is reporting a warning
over CAN bus to the Main
Controller. The warning message
will present a warning code which
corresponds to the warning code
the module is reporting. See the
Governor manual for each
warning message and
description.
The Power Zone Governor
detected a warning in its
operation and
communicated the warning
code to the Main Controller
over CAN bus.
This warning will
automatically clear when
the Power Zone
Governor warning is
resolved.
CAN AVRx
MODULE
WARNING
The Power Zone AVR module #x
is reporting a warning over CAN
bus to the Main Controller. The
warning message will present a
warning code which corresponds
to the warning code the module is
reporting. See the AVR manual
for each warning message and
description.
The Power Zone AVR
detected a warning in its
operation and
communicated the warning
code to the Main Controller
over CAN bus.
This warning will
automatically clear when
the Power Zone AVR
warning is resolved.
CAN BATx
MODULE
WARNING
The Power Zone Battery Charger
#x is reporting a warning over
CAN bus to the Main Controller.
The warning message will
present a warning code which
corresponds to the warning code
the module is reporting. See the
Battery Charger manual for each
warning message and
description.
The Power Zone Battery
Charger detected a
warning in its operation and
communicated the warning
code to the Main Controller
over CAN bus.
This warning will
automatically clear when
the Power Zone Battery
Charger warning is
resolved.
CAN UNKNOWN
MODULE ERROR
A module with an unknown
address reported a warning over
CAN bus with the Main Controller.
There may not be a way to tell
which warning has been triggered
without knowing what module it
came from.
There is a module
communicating over CAN
bus with the Main
Controller that has reported
a warning, but the address
of the module is unknown,
corrupted, or invalid.
This warning will
automatically clear when
the Unknown module
warning is resolved.
Alarm Display Text Description Set Alarm Clear Alarm