Owner’s Manual for Power Zone Pro Sync 57
Troubleshooting
FC DOF GENERATOR POWER Indicates one or more ATSs in the system are in the
Emergency or Generator position.
FC DOF ALL GENERATORS ON LINE All MPS generators are connected to the Power Bus and
communicating.
FC DOF CHECK VOLTAGE PHASE ROTATION Generator voltage sensing phase sequence does not match
the bus voltage sensing phase sequence (i.e. ABC vs.
CBA).
FC DOF FAULT RELAY ACTIVE Becomes active when a new warning alarm or shutdown
alarm is reported.
FC DOF ANNUNCIATOR SPARE LIGHT Spare light state on the remote annunciator. TRUE turns on
the light.
FC DOF GEN COMMS FAILED Communication between MPS Gensets have failed.
FC DOF GFI FAULT A Ground Fault has been detected.
FC DOF GEN DERATED FOR PROTECTION An event has temporarily reduced the rated power of the
generator.
FC DOF GEN IN BACKUP MODE Generator is in MPS Backup Mode.
FC DOF GEN CONNECTED TO BUS IN BACKUP Generator is connected to the bus in MPS Backup Mode.
FC DOF RAP LOW OIL PRESSURE WARNING Remote Annunciator LED LOW OIL PRESSURE
WARNING indicator state.
FC DOF RAP LOW OIL PRESSURE ALARM Remote Annunciator LED LOW OIL PRESSURE ALARM
indicator state.
FC DOF RAP HIGH COOLANT
TEMPERATURE WARNING
Remote Annunciator LED HIGH COOLANT
TEMPERATURE WARNING indicator state.
FC DOF RAP HIGH COOLANT
TEMPERATURE ALARM
Remote Annunciator LED HIGH COOLANT
TEMPERATURE ALARM indicator state.
FC DOF RAP LOW COOLANT
TEMPERATURE WARNING
Remote Annunciator LED LOW COOLANT
TEMPERATURE WARNING indicator state.
FC DOF RAP LOW BATTERY VOLTAGE
WARNING
Remote Annunciator LED LOW BATTERY VOLTAGE
WARNING indicator state.
FC DOF RAP HIGH BATTERY VOLTAGE
WARNING
Remote Annunciator LED HIGH BATTERY VOLTAGE
WARNING indicator state.
FC DOF RAP LOW FUEL WARNING Remote Annunciator LED LOW FUEL WARNING indicator
state.
FC DOF RAP FAIL TO START ALARM Remote Annunciator LED engine FAILED TO START
ALARM indicator state.
FC DOF RAP COOLANT LEVEL ALARM Remote Annunciator LED COOLANT LEVEL ALARM
indicator state.
FC DOF RAP BATTERY CHARGE FAIL ALARM Remote Annunciator LED BATTERY CHARGER FAILED
ALARM indicator state.
FC DOF RAP OVERSPEED SHUTDOWN Engine RPM is too high.
FC DOF TRANSFER SWITCH ERROR ALARM At least one transfer switch has an alarm.
DOF DOF Description

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems Power Zone Pro Sync and is the answer not in the manual?

Generac Power Systems Power Zone Pro Sync Specifications

General IconGeneral
BrandGenerac Power Systems
ModelPower Zone Pro Sync
CategoryController
LanguageEnglish

Related product manuals