Owner’s Manual for Power Zone Pro Sync 59
Troubleshooting
FC DOF IF MPS COMMS FAIL Ethernet communications lost with one or more main
controllers in an MPS.
FC DOF IF THROTTLE STUCK x The throttle stuck alarm is active. “x” can be number 1-4.
FC DOF IF CAN GOVx MISSING MODULE Communications between the Governor and the Main
Controller are bad. “x” can be number 1-4.
FC DOF IF CAN AVRx MISSING MODULE Communications between the AVR and the Main Controller
are bad. “x” can be number 1-4.
FC DOF IF CAN BATx MISSING MODULE Communications between the Battery Charger and the
Main Controller are bad. “x” can be number 1-4.
FC DOF IF CAN GOVx MODULE ERROR Error on the Power Zone Governor has occurred. “x” can be
number 1-4.
FC DOF IF CAN AVRx MODULE ERROR Error on the Power Zone AVR has occurred. “x” can be
number 1-4.
FC DOF IF CAN BATx MODULE ERROR Error on the Power Zone Battery Charger has occurred. “x”
can be number 1-4.
FC DOF IF CAN GOVx ACK ERROR The Power Zone Governor failed to acknowledge a Main
Controller CAN bus message. “x” can be number 1-4.
FC DOF IF CAN AVRx ACK ERROR The Power Zone AVR failed to acknowledge a Main
Controller CAN bus message. “x” can be number 1-4.
FC DOF IF CAN BATx ACK ERROR The Power Zone Battery Charger failed to acknowledge a
Main Controller CAN bus message. “x” can be number 1-4.
FC DOF IF RPM1 SENSOR FAIL RPM sensor fault is active.
FC DOF AI OVER FREQ ALARM Frequency is too high on output voltage.
DOF DOF Description