Appendix
0020177748_03 ENERGY Installation and maintenance instructions 31
Fault code Meaning Possible cause
F.83 Fault: Dry fire When the burner starts, the temperature change registered at the flow or
return temperature sensor is non-existent or too small: Insufficient water
in the product, the flow or return temperature sensor is not in the correct
position on the pipe
F.84 Fault: Flow/return temperature sensor Values not consistent, difference < -6 K
Flow and return temperature sensors signalling implausible values: Flow and
return temperature sensors have been inverted, flow and return temperature
sensors have not been correctly installed
F.85 Fault: Temperature sensor The flow and/or return temperature sensors have been installed on the same
pipe/incorrect pipe
Temperature sensor not connected or is connected incorrectly
F.86 Fault: Underfloor heating contact Underfloor heating contact open, sensor disconnected or defective
F.87 Fault: Electrodes Electrodes not connected or they are connected incorrectly, short circuit in
the cable harness
F.88 Fault: Gas valve Gas valve not connected or it is connected incorrectly, short circuit in the
cable harness
Connection No communication between the PCB
and the user interface
Electronics defective