EasyManuals Logo

Grundfos MAGNA3 Series User Manual

Grundfos MAGNA3 Series
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #93 background imageLoading...
Page #93 background image
25 of 36 © 2009 D 664 - 07/09
B1
T Maximum The maximum ∆T for the snow
melting system.
PRIORITY NONE
10 to 70°F, OFF
(5 to 39°C, OFF)
Default = OFF
C1
Differential The differential for the snow
melting system.
Boil SENS = SUP
AUTO, 2 to 42°F
(AUTO, 1 to 23°C)
Default = AUTO
A
C1
Boiler Minimum The minimum temperature
allowed for the boiler target temperature.
Boil SENS NONE
OFF, 80 to 180°F
(OFF, 27 to 82°C)
Default = 140° (60°C)
C1
Fire Delay The time delay the control can expect
between the time the Boiler contact closes and
the boiler fi res.
Boil SENS = SUP
0:00 to 3:00 minutes
Default = 0:10 min
C1
Boiler Mass The thermal mass characteristics of
the boiler(s) that is being used.
Boil SENS = SUP
LITE, MED, HEVY
Default = MED
C1
Stage 1 Selects stage 1 as operational or not.
Boil SENS = SUP
AUTO, OFF
Default = AUTO
C1
Stage 2 Selects Stage 2 as operational or not.
Boil SENS = SUP
AUTO, OFF
Default = OFF
C1
Rotate Sets the rotation time for the stages.
This item is used by the Equal Run Time
Rotation function.
Boil SENS = SUP
10 to 72 hours,
OFF
Default = 48 hr
A
Exercise The frequency with which the control
exercises the pumps and valves that are operated
by the control.
30 to 240 hours,
(in 10 hour steps)
Default = 70 hr
Item Field
Access
Level
Description
Range
Actual
Setting
Section
LTD
USER
INST
ADV
664 Adjust Menu (3 of 3)

Table of Contents

Other manuals for Grundfos MAGNA3 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos MAGNA3 Series and is the answer not in the manual?

Grundfos MAGNA3 Series Specifications

General IconGeneral
Temperature Range-10 °C to +110 °C
Insulation ClassF
SeriesMAGNA3
Max. Liquid Temperature110 °C
Power Supply1x230V, 3x400V
ApprovalsCE
Pump HousingCast iron
InstallationInline
CommunicationModbus RTU, BACnet MS/TP
Ambient Temperature0 °C to 40 °C
MaterialCast iron

Related product manuals