* Depending on setting
Pressure sensor
(Warning)
Broken FlowControl cable
Sensor defect
Pressure sensor not correctly
calibrated.
Check plug connection.
Change sensor if necessary.
Calibrate pressure sensor correctly
(see section 6.8.2 Calibration of pressure
sensor).
Motor blocked
(alarm)
Backpressure greater than
nominal pressure
Damage to gears
Reduce backpressure.
Arrange for repair of gears, if necessary.
Bus
(Warning/alarm*)
Fieldbus communication error Check cables for correct specification and
damage; replace if necessary.
Check cable routing and shielding; correct
if necessary.
E-Box
(Alarm)
E-Box connection error
Faulty E-Box
Check plug connection.
Replace E-Box if necessary.
Cable break
(Alarm)
Defect in analog cable 4 - 20 mA
(input current < 2 mA)
Check cable/plug connections and
replace, if necessary.
Check signal transmitter.
Service soon/
now
(Warning)
Time interval for service expired Perform service (see section 7.2 Perform
service).
Display in the
’Alarm’ menu
Possible cause Possible remedy