EasyManua.ls Logo

Hach ANATEL PAT700 - 11.3 Data encoding

Hach ANATEL PAT700
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 147
Modbus Protocol
Request
Response
*N = quantity of registers
Error
Any other Function Code request will be returned with an error response indicating the
Function Code is not supported, as well as a request for too much data or data at a
register address that is not present.
11.2.2 TCP/IP interface
The Modbus/TCP interface is attached to the TCP/IP stack that is implemented within the
Anatel PAT700 TOC Analyzer, and will listen to all communications that come in on
Modbus/TCP registered port 502.
The Modbus/TCP client uses the standard TCP methods for communicating with the
driver, as established by the BSD socket interface: connect(), send(), receive() and
close(). Only 1 Server connection is allowed at any time. If there is an active connection,
any attempt at any more connections is ignored.
Once a connection has been established, it will be closed after 90 Seconds of inactivity.
Function Code 1 byte 0x03
Starting Address 2 bytes 0x0000 to 0xFFFF
Quantity of Registers 2 bytes 1 to 125 (0x01 to 0x7D)
Function Code 1 byte 0x03
Byte Count 1 byte 2 x N*
Register Values N* x 2 bytes
Function Code 1 byte 0x83
Exception Code 1 byte

Table of Contents

Other manuals for Hach ANATEL PAT700

Related product manuals