ModBUS Register Information
67
Setup/Relay 3/Event On Min Time 40160
Unsigned
Integer
1 R/W Sets the min on time (mins)
Setup/Relay 3/Event Off Max Time 40161
Unsigned
Integer
1 R/W Sets the max off time (mins)
Setup/Relay 3/Event Off Min Time 40162
Unsigned
Integer
1 R/W Sets the min off time (mins)
Setup/Relay 3/Timer Hold Type 40163
Unsigned
Integer
1R/W
Sets which Sensor outputs are affected
during timer on time (0 = None;
2 = Selected Sensor; 13 = All Sensors)
Setup/Relay 3/Timer Sensor Select 40164
Unsigned
Integer
1R/W
Selects which Sensor outputs are being
held/transferred during the timers on time
(this is used when Hold type is set for
single Sensor)
Setup/Relay 3/Timer Hold Mode 40165
Unsigned
Integer
1R/W
Selects hold outputs vs. set transfer value
during timers on time
Setup/Relay 3/Timer Duration Time 40166
Unsigned
Integer
1 R/W Sets the timer on duration time (sec)
Setup/Relay 3/Timer Period Time 40167
Unsigned
Integer
1R/W
Sets the period between timer on events
(mins)
Setup/Relay 3/Timer Off Delay 40168
Unsigned
Integer
1R/W
Sets the time the affected Sensor outputs
are held/transferred after the timer turns
off (sec)
Setup/Relay 3/Status Level 40169
Unsigned
Integer
1R/W
Sets the status level which will trigger
the relay
Comm/Net Card Mode 40170
Unsigned
Integer
1R/W
Sets the Modbus mode
(0=RTU;1=ASCII)
Comm/Net Card Baud 40171
Unsigned
Integer
1R/W
Sets the Modbus baud rate (0 = 9600;
1 = 19200; 2 = 38400; 3 = 57600;
4 = 115200)
Comm/Net Card Stop Bits 40172
Unsigned
Integer
1 R/W Sets the number of stop bits (1,2)
Comm/Net Card Data Order 40173
Unsigned
Integer
1R/W
Sets the register data order for floats
(0 = Normal; 1 = Reversed)
Comm/Net Card
Min
Response
Time
40174
Unsigned
Integer
1R/W
Sets the minimum response time
(0 to 30 sec)
Comm/Net Card
Max
Response
Time
40175
Unsigned
Integer
1R/W
Sets the maximum response time
(100 to 1000 sec)
Comm/Net
Card/Addresses
sc100 40176
Unsigned
Integer
1 R/W Sets the sc100 Modbus Address
Comm/Net
Card/Addresses
Sensor 1 40177
Unsigned
Integer
1 R/W Sets the Sensor 1 Modbus Address
Comm/Net
Card/Addresses
Sensor 2 40178
Unsigned
Integer
1 R/W Sets the Sensor 2 Modbus Address
Comm/Net Card/Stats
Good
Messages
40179
Unsigned
Integer
2 R/W Number of good messages
Comm/Net Card/Stats
Bad
Messages
40181
Unsigned
Integer
2 R/W Number of failed messages
Comm/Net Card/Stats % Good Mesg 40183 Float 2 R/W % of good messages
Table 14 Controller ModBUS Registers (continued)
Group Name Tag Name Register # Data Type Length R/W Description