66
ModBUS Register Information
Setup/Relay 2/Timer Duration Time 40126
Unsigned
Integer
1 R/W Sets the timer on duration time (sec)
Setup/Relay 2/Timer Period Time 40127
Unsigned
Integer
1R/W
Sets the period between timer on events
(mins)
Setup/Relay 2/Timer Off Delay 40128
Unsigned
Integer
1R/W
Sets the time the affected Sensor outputs
are held/transferred after the timer turns
off (sec)
Setup/Relay 2/Status Level 40129
Unsigned
Integer
1R/W
Sets the status level which will trigger the
relay
Setup/Relay 3 Source 40130
Unsigned
Integer
1R/W
Selects data source for this relay
(0 = None; 1 = Real Time Clock;
2 = Sensor; 4 = Calculation)
Setup/Relay 3 Sensor Select 40131
Unsigned
Integer
1R/W
Selects Sensor source when Source =
Sensor (0 = Sensor1; 1 = Sensor2)
Setup/Relay 3
Measurement
Select
40132
Unsigned
Integer
1R/W
Selects measurement on the Sensor
(0 = Meas1 .. 3 = Meas4)
Setup/Relay 3 Type 40133
Unsigned
Integer
1R/W
Selects the relay type (0 = Alarm; 1 =
Control; 2 = Status; 3 = Timer; 4 = Event)
Setup/Relay 3
Transfer
Setting
40134
Unsigned
Integer
1R/W
Selects the transfer value for the relays
(0 = De-energized; 1 = Energized)
Setup/Relay 3/Alarm High Alarm 40135 Float 2 R/W Sets the high alarm setpoint
Setup/Relay 3/Alarm Low Alarm 40137 Float 2 R/W Sets the low alarm setpoint
Setup/Relay 3/Alarm
High
Deadband
40139 Float 2 R/W Sets the high alarm deadband
Setup/Relay 3/Alarm
Low
Deadband
40141 Float 2 R/W Sets the low alarm deadband
Setup/Relay 3/Alarm On Delay 40143
Unsigned
Integer
1 R/W Sets the on delay time
Setup/Relay 3/Alarm Off Delay 40144
Unsigned
Integer
1 R/W Sets the off delay time
Setup/Relay 3/Control Setpoint 40145 Float 2 R/W Sets the controller setpoint
Setup/Relay 3/Control Phase 40147
Unsigned
Integer
1R/W
Sets the controller phase
(0=Low;1=High)
Setup/Relay 3/Control Deadband 40148 Float 2 R/W Sets the controller deadband
Setup/Relay 3/Control
Overfeed
Timer
40150
Unsigned
Integer
1 R/W Sets the overfeed timer value (mins)
Setup/Relay 3/Control On Delay 40151
Unsigned
Integer
1 R/W Sets the on delay time (sec)
Setup/Relay 3/Control Off Delay 40152
Unsigned
Integer
1 R/W Sets the off delay time (sec)
Setup/Relay 3/Control
Reset
Overfeed
Timer
40153
Unsigned
Integer
1 R/W Resets the overfeed timer
Setup/Relay 3/Event Setpoint 40154 Float 2 R/W Sets the event setpoint
Setup/Relay 3/Event Phase 40156
Unsigned
Integer
1 R/W Sets the event phase (0 = Low; 1 = High)
Setup/Relay 3/Event Deadband 40157 Float 2 R/W Sets the event deadband
Setup/Relay 3/Event On Max Time 40159
Unsigned
Integer
1 R/W Sets the max on time (mins)
Table 14 Controller ModBUS Registers (continued)
Group Name Tag Name Register # Data Type Length R/W Description