ModBUS Register Information
65
Setup/Relay 2 Type 40093
Unsigned
Integer
1R/W
Selects the relay type (0 = Alarm; 1 =
Control; 2 = Status; 3 = Timer; 4 = Event)
Setup/Relay 2
Transfer
Setting
40094
Unsigned
Integer
1R/W
Selects the transfer value for the relays
(0 = De-energized; 1 = Energized)
Setup/Relay 2/Alarm High Alarm 40095 Float 2 R/W Sets the high alarm setpoint
Setup/Relay 2/Alarm Low Alarm 40097 Float 2 R/W Sets the low alarm setpoint
Setup/Relay 2/Alarm
High
Deadband
40099 Float 2 R/W Sets the high alarm deadband
Setup/Relay 2/Alarm
Low
Deadband
40101 Float 2 R/W Sets the low alarm deadband
Setup/Relay 2/Alarm On Delay 40103
Unsigned
Integer
1 R/W Sets the on delay time
Setup/Relay 2/Alarm Off Delay 40104
Unsigned
Integer
1 R/W Sets the off delay time
Setup/Relay 2/Control Setpoint 40105 Float 2 R/W Sets the controller setpoint
Setup/Relay 2/Control Phase 40107
Unsigned
Integer
1R/W
Sets the controller phase
(0=Low;1=High)
Setup/Relay 2/Control Deadband 40108 Float 2 R/W Sets the controller deadband
Setup/Relay 2/Control
Overfeed
Timer
40110
Unsigned
Integer
1 R/W Sets the overfeed timer value (mins)
Setup/Relay 2/Control On Delay 40111
Unsigned
Integer
1 R/W Sets the on delay time (sec)
Setup/Relay 2/Control Off Delay 40112
Unsigned
Integer
1 R/W Sets the off delay time (sec)
Setup/Relay 2/Control
Reset
Overfeed
Timer
40113
Unsigned
Integer
1 R/W Resets the overfeed timer
Setup/Relay 2/Event Setpoint 40114 Float 2 R/W Sets the event setpoint
Setup/Relay 2/Event Phase 40116
Unsigned
Integer
1 R/W Sets the event phase (0 = Low; 1 = High)
Setup/Relay 2/Event Deadband 40117 Float 2 R/W Sets the event deadband
Setup/Relay 2/Event On Max Time 40119
Unsigned
Integer
1 R/W Sets the max on time (mins)
Setup/Relay 2/Event On Min Time 40120
Unsigned
Integer
1 R/W Sets the min on time (mins)
Setup/Relay 2/Event Off Max Time 40121
Unsigned
Integer
1 R/W Sets the max off time (mins)
Setup/Relay 2/Event Off Min Time 40122
Unsigned
Integer
1 R/W Sets the min off time (mins)
Setup/Relay 2/Timer Hold Type 40123
Unsigned
Integer
1R/W
Sets which Sensor outputs are affected
during timer on time (0 = None;
2 = Selected Sensor; 13 = All Sensors)
Setup/Relay 2/Timer Sensor Select 40124
Unsigned
Integer
1R/W
Selects which Sensor outputs are being
held/transferred during the timers on time
(this is used when Hold type is set for
single Sensor)
Setup/Relay 2/Timer Hold Mode 40125
Unsigned
Integer
1R/W
Selects hold outputs vs. set transfer value
during timers on time
Table 14 Controller ModBUS Registers (continued)
Group Name Tag Name Register # Data Type Length R/W Description