43 Channel
Minimum ON Time (Setpoint must be enabled first)
Option: 1 to 10 seconds
Allows users to control the speed of the relay status change when previously set conditions are met. This timer
prevents the relay and connected device from “chattering” by forcing a minimum on and off time.
The flashing of the selected value indicates that it can be modified by using the
ud keys.
With Minimum ON Time selected, press Set.
Press the
ud keys to edit the value displayed blinking. Press CFM to save
Note: The controller validates the configured Setup when attempting to exit menu and directs the user to any
invalid parameters. At prompt to save changes, press virtual key YES.
6.3.2. Configurable Alarm Settings
This submenu is used to define the operating limits of the process. The setting thresholds configured in this
submenu control the Alarm relay. If Alarm becomes active, control stops. Both measured parameter and
Temperature are configured in this submenu.
Note: Alarm Menu items are measurement specific. Examples are given using pH, however, actual units will
depend on the probe connected and on the probe configuration (e.g. mode, units etc).
Navigation
• Press
b key from the Measure mode.
• Press Setup from Channel parameter.
• Press Setup with Alarm Settings highlighted, and the alarm submenu will open.
• Press the
ud keys to move between options.
• Press the back key (
b ) to return to the menu without saving.
Enable
b
Setup
Note: We suggest users make configuration changes from the beginning of the menu structure going forward,
because the menu references parameters that were set earlier in the submenu.
` At prompt, enter the passcode.
` At prompt, press YES to place unit in HOLD.
When completed, return to the “other” parameter and set that up also. Alarm can be configured for both
measurement and Temperature.