HI 1756-WS WEIGH SCALE MODULE
4-14
Channel Number: 0 or 1
Number of Elements: 8
Error Return Values: None
Cal Low Command
(CALLOWCMD)
The Cal Low Command sets the “calLowCount”
parameter to the current A/D average counts when
doing a hard calibration. An Integrated Technician
function gets called during low calibration.
Command Number: 0x64 (Hexadecimal)
Channel Number: 0 or 1
Number of Elements: 8
Error Return Values:
STATUSWORD - there was a conversion error,
weight in motion or an A/D error or all three.
HARDCALFAILCOUNTS - less than 100
counts between the zero and the span weights.
Cal High
Command
(CALHIGHCMD)
The Cal High Command - Sets the Span Weight
parameter to the current A/D average counts when
doing Hard CAL.
Command Number: 0x65 (Hexadecimal)
Channel Number: 0 or 1
Number of Elements: 8
Error Return Values:
STATUSWORD - there was a conversion error,
weight in motion or an A/D error or all three.
HARDCALFAILCOUNTS - there are less than
100 counts between the zero and the span
weights.
C2 Cal Command
(C2CALCMD)
The C2 Cal Command - Performs a C2 Calibration.
Uses CalLowWeight as the reference point.
Command Number: 0x66 (Hexadecimal)
Channel Number: 0 or 1
Number of Elements: 8