MPC Platinum Installation and Operation Manual
HT# 059085-00 F
INTERNET ALARMS
be activated through the Internet ICMS website by visiting the control Alarm
Activate any alarm by creating at least one delivery. Simply, click on the Alarm
button. Then, add a delivery by clicking on the Add Delivery button on the right
hand side of the screen. A delivery method option (Web or e-mail) must be selected
subject, e-mail, and message.
A delivery can be in the form of a web alarm (the building and control icons will have
a Red dot), an e-mail alarm, a text message to a cell phone (it is an e-mail in the form
of 1111111111@CellCompany.com where "CellCompany.com" portion will vary with
the cell phone carrier).
The MPC Platinum control alarms are:
(#1000) In Bypass for Over 1 Hour: This alarm generates if the control has been
set to Bypass either locally (Auto/bypass switch) or remotely for a full continuous
hour. See "AUTO/BYPASS Switch" on page 16.
(#6000) Is an end alarm that can be set to indicate that the initial alarm status has
terminated.
(#1001) Heat Established Taking More than 1 hour: This alarm will be sent only if
the establishing heat took longer than 1 hour.
(#6001) Is an end alarm that can be set to indicate that the initial alarm status has
terminated.
(#1002)/(#1003) Space Temp Exceeds/Below Target by More Than 10°: This alarm
generates if the space average over the past two hours has averaged 10°F above or
below the space target.
(#6002)/(#6003) Is an end alarm that can be set to indicate that the initial alarm
status has terminated.
Internet control web Control Alarms
(#1006) System Sensor Fault: This alarm generates whenever the System sensor
reads open or short.
(#6006) Is an end alarm that can be set to indicate that the initial alarm status has
terminated.
(#1008) No prove for More Than 10 Minutes: This generates whenever there is a
call for output but the Prove terminals have not been shorted for over 10 minutes.
(#6008) Is an end alarm that can be set to indicate that the initial alarm status has
terminated.
(#1012) The DHW-ES (Purchased separately (HT# 926769-00)) has no
communication for 1 minute.
(#6012) Is an end alarm that can be set to indicate that the initial alarm status has
terminated.
(#3000) The Platinum control could not establish a dependable two way
communication with the Heat-Timer Servers for over 24 hours.
(#8000) Is an end alarm that can be set to indicate that the initial alarm status has
terminated.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the heat-timer MPC Platinum and is the answer not in the manual?

heat-timer MPC Platinum Specifications

Power IconPower
voltage input120 VAC 60 Hz
power consumption30 VA Max/30 Amp Max
output relay ratings1 Amp inductive, 6Amp resistive at 120 VAC 60 Hz, 15A total for all circuits
Temperature Control IconTemperature Control
temperature displayFahrenheit or Celsius
sensor ranges-35°F/-37°C to 250°F/121°C
system set point70°F/21°C to 250°F/121°C
Weight and Dimensions IconWeight and Dimensions
dimensions5-1/8” x 13" x 13"
weight14 pounds