MPC Platinum Installation and Operation Manual
7
HT# 059085-00 F
Vacation Schedule (Available with Internet Control Only)
This feature gives the user the ability to provide a lower-than-night space target between two specied date-time combinations.
This provides additional savings for schools and ofce buildings to use in long holiday periods. See "Vacation Schedule Setting"
on page 30.
Space Sensor Feedback (Available with Internet Control Only)
For better control and much more energy saving capabilities you can add wireless or wired space sensors to the MPC Platinum to
ne tune its operation and increase the system's overall efciency. When you add space sensors to the space average, the MPC
Platinum checks the space average before the beginning of each cycle to determine if the building is sufciently heated. See
"Space Lockout" on page 28.
System Output
The system output relay connects to and operates a combustion air-damper or other boiler room equipment and it will energize
whenever there is a call for the boiler. In addition, if you connect the combustion air-damper's end-switch to the Prove input
terminals, it will stop the boiler from ring if the damper is not fully open. See "Installation" on page 8.
Boost and Early Shutdown
The boost returns the building to its Day (Normal) heat level after Night (Setback) heat level. It does it by running the burner
or valve output for a period of time that depends on the outside temperature. It offers an adjustable curve parameter to tune its
operation to the specic building. See "Boost Mode" on page 26.
The Early Shutdown feature shifts the Day schedule to Night Setback before the last Night Time setting for that day. The Early
Shutdown varies based on Outdoor temperature (OD). The warmer the Outdoor temperature the earlier the MPC Platinum shifts to
Night Setback. See "Early Shutdown Curves" on page 27.
Remote Communication
The MPC Platinum is upgradable to Internet, BACnet IP, BACnet MSTP, or MODBUS communication to allow monitoring and
controlling of all of its functions from a remote location. Only the Internet communication package allows the MPC Platinum to
accept a variety of additional sensor inputs to monitor their status and provide web, E-Mail, or text message alarms under specied
adjustable conditions.
MAKING SURE YOU HAVE THE RIGHT CONTROL
If you need the MPC Platinum to do additional tasks that either are not listed or you do not know how to congure them,
contact Heat-Timer Corp. Sales Department either by Phone (973)575-4004, Fax (973) 575-4052, or over the web (visit
http://www.heat-timer.com).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the heat-timer MPC Platinum and is the answer not in the manual?

heat-timer MPC Platinum Specifications

Power IconPower
voltage input120 VAC 60 Hz
power consumption30 VA Max/30 Amp Max
output relay ratings1 Amp inductive, 6Amp resistive at 120 VAC 60 Hz, 15A total for all circuits
Temperature Control IconTemperature Control
temperature displayFahrenheit or Celsius
sensor ranges-35°F/-37°C to 250°F/121°C
system set point70°F/21°C to 250°F/121°C
Weight and Dimensions IconWeight and Dimensions
dimensions5-1/8” x 13" x 13"
weight14 pounds