EasyManua.ls Logo

heat-timer MPC Platinum - MODBUS Communication Features; MODBUS Communication Options; MODBUS RTU Communication con Iguration; MAC Address

heat-timer MPC Platinum
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MPC Platinum Installation and Operation Manual
41
HT# 059085-00 F
MODBUS COMMUNICATION FEATURES
The MPC Platinum BUS (with MODBUS RTU connections) has many features and benets.
Boiler and Sensor status, values, and settings. Provides “Live” status and editing capability of Platinum control settings and values
from the MODBUS network.
The Data collected can be used to create a historical log, and trigger alarms.
MODBUS RTU COMMUNICATION CONFIGURATION
If the Platinum control is purchased with or upgraded to a MODBUS communication, the
following settings must be congured to guarantee proper communication.
--NETWORK SETTINGS--
MAC Address 1
Baud 9600
MODBUS COMMUNICATION OPTIONS
SELECT: MENU/<Settings>/<More Settings>/<Remote Interface>/Network Setting
Before connecting the Platinum control to the MODBUS network, the user must set the following parameters according to the
MODBUS Network Administrator's instructions.
MAC ADDRESS
Options: From 1 to 247 Default: 1
This is a unique ID within the MODBUS network. It must be provided by the MODBUS
Network Administrator.
---- MAC ADDRESS ---
1
[
]
MODBUS BAUD
Options: 9600, 19200, 38400 Default: 9600
The Baud determines the speed of communication.
Both the Platinum control and BMS must use the same Baud rate.
The communication is xed to 8 Data Bits, No Parity, and 2 Stop Bits.
------ BAUD RATE -----
9600
19200
38400
ALERT
MODBUS capable Platinum controls will display --NETWORK PANEL--
on the 2nd row of the display when in screen saver mode.
MPC PLATINUM MODBUS VARIABLE LIST
MULT
1
(if not 1)
UOM
READ
ONLY
MPC
Platinum REG
/ VARIABLE#
1 – 3
DESCRIPTION
Model
RANGE / STATES / SPECIAL
VALUES
6 Character string
3
X
4 – 13 Serial Number 20 Character string
3
X
14 Firmware Version 100 X
15 Vari-Boost Adjustment 10 none 0.1 – 6.4
16 Boost Mode
0=Disabled, 1=Manual,
2=Vari, 3=Vari+ESD
17 Manual Boost Time Minutes 0 – 120
18,19 Bypass Time Minutes 0 – 2,147,483,647
4
X
20 Bypass Mode 0=AUTO, 1=ON
21 Cycle Length Minutes 10 – 240
22 Day Heat Adjustment 0 – 15 = A – P
23 Outdoor Day Cutoff °C, °F -6 – 38°C, 20 – 100°F
24 Day Light Saving 0=Enable, 1=Disable
25 Sensor Fault Mode 0=OutputOn, 1=OutputOff
26 System Differential °C, °F 2 – 42°C, 3 – 75°F
27 Sensor Mode 0=°F, 1=°C

Table of Contents

Related product manuals