Indverter V2 Manual
Issue 03 Dated 11 November 2009 S/w Ver 12.4 HEXMOTO
Controls Pvt.Ltd
37
29-30 JOG Acc – JOG Dec
Acceleration and deceleration times set here are selected by the drive if JOG terminal on control TB is
activated. This selection remains as long as JOG is enabled.
31 JOG Frequency
This is the set frequency for JOG Operation. JOG operation is enabled if JOG terminal on control TB is
activated along with FOR/REV terminals. Direction of JOG rotation is from FOR/REV terminals on control
TB. JOG input overrides all other frequency reference selections.
32 -- 38 Multi speed selection
This value will be reference frequency depending on the digital inputs X1, X2 and X3. If main speed
reference selection in Para 03 is 0005 or 0006(Raise / Lower), Multi speed is not operational. Also, when
Auto run mode Para 40 is enabled, Multi speed is not operational. JOG input overrides X1,X2 X3 selection.
0 = open 1 = Closed
39 Arun Direction
This parameter assigns direction for each step of Auto run operation. Parameter 39 is applicable to all Auto
Run modes of operation in Para 40. For selection 0000, direction is controlled by FOR/REV TB Input to the
drive controller. All other selections override TB direction input and follow programmed direction in this
parameter. On completion of Auto run cycle, direction from TB input is followed.
40 Arun Mode
Auto run is enabled using this parameter. Para 41- 44 determines the motor speed, time duration and ramp
value for each step of Auto run operation. If the Inverter Stops and Starts again, it will begin a new Auto
Run Cycle.
41- 44 Arun Step-1 time – Arun Step-4 time
Drive runs for time in seconds programmed here for each step in auto run mode. Setting this as 0000
disables the current and next step in Auto run cycle. Para 32 to 35 determines frequency reference for
Step-1 to Step-4. Para 72 to 75 determines the Acceleration/ Deceleration times for Step-1 to Step-4.
X1 X2 X3 Speed Reference Function code
0 0 0 Main-Speed-Ref Para 03
1 0 0 Multi speed 1 Para 32
0 1 0 Multi speed 2 Para 33
1 1 0 Multi speed 3 Para 34
0 0 1 Multi speed 4 Para 35
1 0 1 Multi speed 5 Para 36
0 1 1 Multi speed 6 Para 37
1 1 1 Multi speed 7 Para 38
Frequency
0
Para 32
Para 33
Para
41
STEP 1 STEP 2
A
CC
Para
72
Para
42
Para
75
DEC
Para
73
A
CC
Para
74
Para 34
Para
43
STEP 3
A
CC
Para
44
Time
STEP 4
Para 35