4.
Bury cables.
Note
●
Interconnecng cable (available for two pedestals and above): The recommended length is L
+1.5 m.
Network communicaon cable: It is recommended to use CAT5e or the network cable has
beer performance.
●
The suggested external diameter of the low voltage conduit is 30 mm.
●
If more peripherals are required to connect, you should increase the conduit diameter or bury
another conduit for the external cables.
●
Before digging holes, evaluate the thickness of the
installaon surface to avoid puncturing.
●
When slong on the installaon surface, pay aenon to the posion and width of the slot to
avoid misalignment of the barrier.
●
One distribuon cabinet supplies one pedestal.
The maximum allowable diameter of the power cable is 12 AWG (UL1015), and the
transmission distance is 100 m.
One
distribuon cabinet supplies two pedestals.
The maximum allowable diameter of the power cable is 16 AWG (UL1015), and the
transmission distance is 25 m.
DS-K3BC430LX Series Swing Gate
5