F3 DIO 16/8 01 3 Product Description
HI 800 177 E Rev. 1.01 Page 27 of 58
Digital outputs
Number of outputs 8 (non-galvanically isolated)
Two-pole switching
DO+ 2A (inrush current typ. 10 A at 2 ms)
DO- 2A (inrush current typ. 10 A at 2 ms)
Output voltage L+ minus voltage drop (L+ and L- leg)
Voltage drop
Two-pole outputs
max. 3 V at 2A
Voltage drop
Outputs DO+
max. 1.5 V at 2A
Voltage drop
Outputs DO-
max. 1.5 V at 2A
Output current
See also
Table 11
max. 2 A at 40 C°
max. 1 A at 60 C°
min. 10 mA
Total permissible current max. 8 A
Leakage current (with low level) max. 1 mA at 2 V
Lamp load max. 25 W
Inductive load max. 500 mH
Open-circuit
> 4 kΩ
Line diagnosis
Short-circuit
< 10 Ω
Behavior with overload The affected output is switched off and
cyclically switched on again
Table 14: Specifications for the Digital Outputs
Pulsed outputs
Number of outputs 2 (non-galvanically isolated)
Output voltage
L+ minus 4 V
Output current approx. 60 mA
Minimum load None
Switching time
100 μs
Behavior with overload
2 x 19.2 V, short-circuit current 60 mA at 24 V
Table 15: Specifications for the Pulsed Outputs

Table of Contents