F3 DIO 16/8 01 4 Start-Up
HI 800 177 E Rev. 1.01 Page 35 of 58
System Signal
Data
type
R/W Description
Module Error Code WORD R Module error code
Coding Description
0x0000 I/O processing, if required with errors
see other error codes
0x0001 No I/O processing (remote I/O not in RUN)
0x0002 No I/O processing during the booting test
0x0004 Manufacturer interface operating
0x0010 No I/O processing: wrong configuration
0x0020 No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module SRS UDINT R Slot number (System Rack Slot)
Module Type UINT R Type of module, target value: 0x00E2 [226
dez
]
1)
LS/LB (short-circuit/open-circuits)
Table 21: SILworX - System Parameters for Digital Inputs, Module Tab
4.3.2.2 DI 16 LC: Channels Tab
The DI 16 LC: Channels tab contains the following system parameters.
System Signal
Data
type
R/W Description
Channel no. --- R Channel number, defined by default
-> Error Code
[BYTE]
BYTE R Error codes for the digital input channels
Coding Description
0x01 Fault in the digital input module
0x10 Short-circuit of the channel
0x80
Intermittence between pulsed output TO and
digital input DI, e.g.,
Open-circuit
Open switch
L+ low voltage
-> Value [BOOL] BOOL R Input values for the digital input channels
0 = input de-energized
1 = input energized
Pulsed Channels
[USINT] ->
USINT W Source channel for pulsed supply
Coding Description
0 Input channel
1 Pulse of the 1st TO channel
2 Pulse of the 2nd TO channel
Table 22: SILworX - System Parameters for Digital Inputs, DI 16 LC: Channels Tab