F3 DIO 16/8 01 4 Start-Up
HI 800 177 E Rev. 1.01 Page 29 of 58
4 Start-Up
To start up the remote I/O, it must be mounted, connected and configured in the
programming tool.
4.1 Installation and Mounting
The remote I/O is mounted on a 35 mm DIN rail such as described in the HIMatrix System
Manual for Compact Systems.
4.1.1 Installation and Terminals of the Digital Inputs
Terminal Designation Function
33, 34 LS+
Sensor supply for inputs 1...4,
buffered/unbuffered supply.
35 1 Digital input 1
36 2 Digital input 2
37 3 Digital input 3
38 4 Digital input 4
39, 40 L- Ground
41, 42 PA Shielding
Terminal Designation Function
43, 44 LS+
Sensor supply for inputs 5...8,
buffered/unbuffered supply.
45 5 Digital input 5
46 6 Digital input 6
47 7 Digital input 7
48 8 Digital input 8
49, 50 L- Ground
51, 52 PA Shielding
Terminal Designation Function
53, 54 LS+
Sensor supply for inputs 9...12,
buffered/unbuffered supply.
55 9 Digital input 9
56 10 Digital input 10
57 11 Digital input 11
58 12 Digital input 12
59, 60 L- Ground
61, 62 PA Shielding
Terminal Designation Function
63, 64 LS+
Sensor supply for inputs 13...16,
buffered/unbuffered supply.
65 13 Digital input 13
66 14 Digital input 14
67 15 Digital input 15
68 16 Digital input 16
69, 70 L- Ground
71, 72 PA Shielding
Table 17: Terminal Assignment for the Digital Inputs