4 Start-Up F3 DIO 16/8 01
Page 46 of 58 HI 800 177 E Rev. 1.01
4.6 Connection Variants
This chapter describes the correct wiring of device in safety-related applications.
4.6.1 One-Pole Connection
For 1-pole applications, the outputs DO+ must be connected to supply S- (load on S-) and
the outputs DO- must be connected to the supply S+ (load on S+).
In this case, 8 outputs DO+ and 8 outputs DO- are available.
No line diagnosis is possible for one-pole applications.
i
A direct connection of the DO+ output to the external L- via the load or a connection of DO-
output to external L- via the load is not permitted!
Inductive loads may be connected with no free-wheeling diode on the actuator. However,
HIMA strongly recommends connecting a protective diode directly to the actuator.
Actuator Free-Wheeling Diode
Figure 11: One-Pole Connection of an Actuator to the DO+ or DO- Output