F3 DIO 16/8 01  4 Start-Up 
HI 800 177 E Rev. 1.01  Page 45 of 58 
4.4.5  Pulsed Outputs for F3 DIO 16/8 01 
System Signal  R/W  Description 
Mod.SRS [UDINT]  R  Slot number (System Rack Slot) 
Mod. Type [UINT]  R  Type of module, target value: 0x00D3 [211
dec
] 
Module error code 
0x0000 
I/O processing, if required with errors, see other error 
codes  
0x0001  No I/O processing (remote I/O not in RUN)  
0x0002  No I/O processing during the booting test 
0x0004  Manufacturer interface operating 
0x0010  No I/O processing: wrong configuration 
0x0020  No I/O processing: fault rate exceeded 
Mod. Error Code [WORD]  R 
0x0040/
0x0080 
No I/O processing: configured module not plugged in 
Error code of the TO unit as a whole DO.Error Code [WORD]  R 
0x0001  Error of the TO unit as a whole: 
Error code of the individual digital pulsed output channels: 
DO[xx].Error Code 
[BYTE] 
R 
0x01  Fault in the digital output module 
Output value for TO channels: 
0 Output de-energized 
1 Output energized 
DO[xx].Value [BOOL]  W 
Do not use pulsed outputs as safety-related outputs! 
Table 29:  ELOP II Factory - System Signals for the Pulsed Outputs 
 
4.5  Configuration of Line Diagnosis 
To diagnose the line for ohmic capacitive loads, the remote I/O sends a 10V test pulse 
(reduced voltage level) to the output circuit for the duration of the monitoring time. This type 
of line diagnosis is particularly recommended for ohmic and ohmic capacitive loads. With 
inductive loads or lamp loads, error messages  related to the short-circuit may be 
generated. 
To configure the line diagnosis, the following parameters must be set in SILworX and the 
following signals must be set in ELOP II Factory Hardware Management. 
SILworX  ELOP II Factory  Value 
DO.LS/LB Interval  DO.LSLB Interval 
Free configurable 
1…100 s 
DO.Line Monitoring Time  DO.LSLB Monitoring Time 
Free configurable 
0…50 ms 
Default: 0 ms 
Two-Pole [BOOL] ->  DO[xx].Two-Pole  TRUE 
Line Monitoring [BOOL] ->  DO[xx].LSLB Monitoring  TRUE 
DO[XX].LS Monitoring with 
red. voltage 
DO[XX].LS Monitoring with 
red. voltage 
TRUE 
Table 30:  Configuration of Line Diagnosis with Reduced Voltage with Ohmic Capacitive 
Loads