F3 DIO 16/8 01 4 Start-Up
HI 800 177 E Rev. 1.01 Page 45 of 58
4.4.5 Pulsed Outputs for F3 DIO 16/8 01
System Signal R/W Description
Mod.SRS [UDINT] R Slot number (System Rack Slot)
Mod. Type [UINT] R Type of module, target value: 0x00D3 [211
dec
]
Module error code
0x0000
I/O processing, if required with errors, see other error
codes
0x0001 No I/O processing (remote I/O not in RUN)
0x0002 No I/O processing during the booting test
0x0004 Manufacturer interface operating
0x0010 No I/O processing: wrong configuration
0x0020 No I/O processing: fault rate exceeded
Mod. Error Code [WORD] R
0x0040/
0x0080
No I/O processing: configured module not plugged in
Error code of the TO unit as a whole DO.Error Code [WORD] R
0x0001 Error of the TO unit as a whole:
Error code of the individual digital pulsed output channels:
DO[xx].Error Code
[BYTE]
R
0x01 Fault in the digital output module
Output value for TO channels:
0 Output de-energized
1 Output energized
DO[xx].Value [BOOL] W
Do not use pulsed outputs as safety-related outputs!
Table 29: ELOP II Factory - System Signals for the Pulsed Outputs
4.5 Configuration of Line Diagnosis
To diagnose the line for ohmic capacitive loads, the remote I/O sends a 10V test pulse
(reduced voltage level) to the output circuit for the duration of the monitoring time. This type
of line diagnosis is particularly recommended for ohmic and ohmic capacitive loads. With
inductive loads or lamp loads, error messages related to the short-circuit may be
generated.
To configure the line diagnosis, the following parameters must be set in SILworX and the
following signals must be set in ELOP II Factory Hardware Management.
SILworX ELOP II Factory Value
DO.LS/LB Interval DO.LSLB Interval
Free configurable
1…100 s
DO.Line Monitoring Time DO.LSLB Monitoring Time
Free configurable
0…50 ms
Default: 0 ms
Two-Pole [BOOL] -> DO[xx].Two-Pole TRUE
Line Monitoring [BOOL] -> DO[xx].LSLB Monitoring TRUE
DO[XX].LS Monitoring with
red. voltage
DO[XX].LS Monitoring with
red. voltage
TRUE
Table 30: Configuration of Line Diagnosis with Reduced Voltage with Ohmic Capacitive
Loads