4 Start-Up  F3 DIO 16/8 01 
Page 38 of 58  HI 800 177 E Rev. 1.01 
4.3.3.2  DO 8 03: Channels Tab 
The DO 8 03: Channels tab contains the following system parameters. 
System Signal 
Data 
type 
R/W  Description 
Channel no.  ---  R  Channel number, defined by default 
-> + Error Code 
[WORD] 
WORD R 
-> - Error Code 
[WORD] 
WORD R 
Error codes for the digital output channels DO+ 
Error codes for the digital output channels DO- 
 
Coding  Description 
0x0001  Fault in the digital output module 
0x0002  Channel shutdown due to overload 
0x0004  Error while reading back the digital outputs 
0x0008 
Error while reading back the status of the 
digital outputs  
0x0010 Short-circuit 
0x0020 
Channel is switched off due to fault on the 
corresponding channel 
0x0040  Z-diode are destroyed at the output 
0x0080 Open-circuit 
0x0100 
MOT test of the output switches provides in 
DO+ line causes an error 
0x0200 
MOT test of the output switches provides in 
DO- line causes an error 
0x0400 
MOT test of the test switches L- causes an 
error 
0x0800  External supply L+ at DO+ 
 
+ Value [BOOL]  BOOL  W  Output value for DO+ channels, one-pole (value: 0 or 1) 
Output value for DO+ channels, two-pole, identical to DO- 
(Value: 0 or 1) 
- Value [BOOL]  BOOL  W  Output value for DO- channels, one-pole (value: 0 or 1) 
Output value for DO- channels, two-pole, identical to DO+ 
(Value: 0 or 1) 
Two-Pole [BOOL]  BOOL  W  Configuration for a two-pole channel 
Coding  Description 
FALSE  Channel used for a 1-pole 
TRUE  Channel used for a 2-pole 
 
Line Monitoring 
[BOOL] -> 
BOOL  W  Configuration of line diagnosis 
Coding  Description 
FALSE LSLB
1) 
diagnosis is not performed 
TRUE LSLB
1)
 diagnosis is performed 
 
1)
 LS/LB (short-circuit/open-circuits) 
Table 24:  SILworX - System Parameters for Digital Outputs, DO 8 03: Channels tab