4 Start-Up F3 DIO 16/8 01
Page 34 of 58 HI 800 177 E Rev. 1.01
4.3.2.1 Module Tab
The Module tab contains the following system parameters.
System Signal
Data
type
R/W Description
DI number
Pulsed Channels
USINT W Number of pulsed outputs (supply outputs)
Coding Description
0
No pulsed output planned for LS/LB
1)
detection
1
Pulsed output 1 planned for LS/LB
1)
detection
2
Pulsed outputs 1 and 2 planned for LS/LB
1)
detection
Pulsed outputs must not be used as safety-related
outputs!
DI Supply [01] BOOL W
DI Supply [02] BOOL W
Triggering the single DI supplies
Coding Description
FALSE Sensor Supply (1 A) is off.
TRUE Sensor supply (1 A) is on.
Default setting FALSE: Deeding current 40 mA
DI Pulse
Slot
UDINT W Pulse module slot
(LS/LB
1)
detection), set the value to 3
DI Pulse Delay (10E-
6s)
UINT W
Waiting time for line control (detection of short-circuits or
cross-circuits)
DI.Error Code WORD R Error codes for all digital inputs
Coding Description
0x0001 Fault within the digital inputs
0x0002 FTT test of test pattern faulty
DI.Error Code
Supply
WORD R Error code of the DI supply unit as a whole:
Coding Description
0x0001 Module fault
DI[01].Error Code
Supply
BYTE R
DI[02].Error Code
Supply
BYTE R
Triggering the single DI supplies
Coding Description
0x01 Error DI supply unit
0x02 Supply shutdown due to over current
0x04 Error while reading back the supply