F3 DIO 16/8 01 4 Start-Up
HI 800 177 E Rev. 1.01 Page 43 of 58
4.4.4 Digital Outputs of F3 DIO 16/8 01
System Signal R/W Description
Mod.SRS [UDINT] R Slot number (System Rack Slot)
Mod. Type [UINT] R Type of module, target value: 0x00C4 [196
dec
]
Module error code
0x0000
I/O processing, if required with errors, see other error
codes
0x0001 No I/O processing (remote I/O not in RUN)
0x0002 No I/O processing during the booting test
0x0004 Manufacturer interface operating
0x0010 No I/O processing: wrong configuration
0x0020 No I/O processing: fault rate exceeded
Mod. Error Code [WORD] R
0x0040/
0x0080
No I/O processing: configured module not plugged in
Error codes for all digital outputs
0x0001 Fault within the digital outputs
0x0002 MOT test of safety shutdown returns a fault
0x0004 MOT test of auxiliary voltage returns a fault
0x0008 FTT test of test pattern faulty
0x0010 MOT test of output switch test pattern faulty
0x0020 MOT test of output switch test pattern
(shutdown test of the outputs) faulty
0x0040 MOT test active shutdown via WD faulty
0x0080 FTT test of monitoring time returns a fault
0x0100 FTT read back of monitoring time returns a fault
0x0200 All outputs are switched off, total current exceeded
0x0400 FTT test: 1st temperature threshold exceeded
0x0800 FTT test: 2nd temperature threshold exceeded
0x1000
FTT test: Monitoring of auxiliary voltage 1:
Low voltage
0x2000
FTT test: Monitoring of auxiliary voltage 2:
Low voltage
0x4000
Flipflop of the voltage monitoring (18V) provides low
voltage
DO.Error Code [WORD] R
0x8000 MOT test of monitoring time returns a fault
Error codes for the digital output channels DO+
Error codes for the digital output channels DO-
0x0001 Fault in the digital output module
0x0002 Channel shutdown due to overload
0x0004 Error while reading back the digital outputs
0x0008
Error while reading back the status of the digital
outputs
0x0010 Short-circuit
0x0020
Channel is switched off due to fault on the
corresponding channel
0x0040 Z-diode at the output destroyed
0x0080 Open-circuit
0x0100
MOT test of the output switches provides in DO+ line
causes an error
0x0200
MOT test of the output switches provides in DO- line
causes an error
DO[xx].+Error Code
DO[xx].-Error Code
[WORD]
R
R
0x0400 MOT test of the test switches L- causes an error