8
Installation BAT
Release
 
05
 
03/2013
When operating the BAT54/300-Rail types in Ex zone 2, the following 
applies:
II 3G
Ex nA IIC T4 Gc, -30 °C ... +50 °C
DEKRA 11ATEX0007 X
DO NOT OPEN WHEN ENERGIZED.
DO NOT USE THE 12 VDC INPUT, WHEN OPERATING THE DEVICE 
IN HAZARDOUS LOCATIONS.
Relevant for use in Hazardous Locations (Class 1 Division 2): 
Only products labeled accordingly may be operated in Class 1 Division 2 
Hazardous Locations.
When operating the BAT54/300-Rail FCC types in Class 1 Division 2 
Hazardous Locations, the following applies:
CLASS I; DIV. 2
GROUPS A; B; C AND D
TEMPERATURE CODE T4
AMBIENT -30 °C ... +50 °C
List of Standards: FM3600, FM3611
DO NOT OPEN WHEN ENERGIZED.
DO NOT USE THE 12 VDC INPUT, WHEN OPERATING THE 
DEVICE IN HAZARDOUS LOCATIONS.
Special conditions for safe use
 Provisions shall be made to prevent the rated voltage from being 
exceeded by transient disturbances of more than 40 %.
 When the temperature under rated conditions exceeds 70 °C at the 
cable or conduit entry point, or 80 °C at the branching point of the 
conductors, the temperature specification of the selected cable shall 
be in compliance with the actual measured temperature values.
Temperature Code T4 Ambient -30 °C … +50 °C
List of Standards EN 60079-0: 2009
EN 60079-15: 2010