Installation MACH104
Release
 
07
 
07/2014
27
3 Basic set-up
Note: Two or more devices configured with the same IP address can cause 
unpredictable operation of your network.
Install and maintain a process that assigns a unique IP address to every 
device in the network.
When you install the device for the first time enter the IP parameters. 
The device provides the following options for entering the IP parameters 
during the first installation:
 Configuration via DHCP (state on delivery)
 Entry via V.24 connection
 Entry with the aid of the HiDiscovery logs on the applications HiDiscovery 
or Industrial HiVision
 Configuration via BOOTP
 Configuration via DHCP (Option 82)
 AutoConfiguration Adapter
Further information on the basic settings of the device can be found in the 
“Basic Configuration” user manual on the CD/DVD.
3.1 Default settings
 IP address: The device looks for the IP address using DHCP
 Management password: 
user, password: public (read only)
admin, password: private (read and write)
 V.24 data rate: 9,600 Baud
 Ring redundancy: off
 Ethernet ports: link status is not evaluated (signal contact)
 Optical 100 Mbit/s ports: 100 Mbit/s full duplex
All other ports: autonegotiation
 Redundancy manager switched off 
(DIP switch RM and Stand-by: ON)
 Stand-by coupling switched off
(DIP switch RM and Stand-by: ON)
Port 3 = control port, port 4 = coupling port for redundant ring coupling
 Rapid Spanning Tree: on