Use in Hazardous Locations
Relevant for use in Hazardous Locations (Class 1, Division 2)::
This equipment is suitable for use in Class 1, Division 2, Groups A, B, C
and D or Non-Hazardous (unclassified) locations only.
When used in Class 1 Division 2 Hazardous Locations, the following
applies:
CLASS I; DIV. 2
GROUPS A; B; C; D
TEMPERATURE CODE T4
AMBIENT -30 °C ... +70 °C
List of Standards: ISA 12.12.01:2007, CSA C22.2 No. 213-
M1987
This equipment must be installed in a tool-locked enclosure when the
USB port will be used.
Warning: Do not remove or replace while circuit is live unless
the area is known to be free of ignitable concentrations or
flammable substances.
Avertissement - Risque d'explosion - Ne pas débrancher tant que le
circuit est sous tension à moins que l'emplacement soit connu pour ne
contenir aucune concentration de gaz inflammable.
Avertissement - Risque d'explosion - La substitution de tout composant
peut rendre ce matériel incompatible pour une utilisation en classe I,
division 2.